Autonics Temperature Controller TCN4S-24R
Autonics Temperature Controller TC4S-24R
Type: Economical Dual Display
Power Supply: 110 - 220 VAC
Dimensions: 48 x 48 mm
Control Output: Relay+SSR (AC/DC power), Relay+SSRP (AC power)
Alarm Output: Alarm1+Alarm2
Made in Korea
Security policy
Delivery policy
Return policy
Display method: 4-digit 7-segment LED
Control method: ON/OFF control, P, PI, PD, PID control
Input specification: Thermocouple: K(CA), J(IC), T(CC), R(PR), S(PR), L(IC)
RTD: DPt100Ω, Cu50Ω
Sampling cycle: 100ms
Control output: Relay (250VAC~ 3A) or SSR drive (12VDC ) [ON/OFF]
Option output: Alarm 1/2
Power supply: 100-240VAC~ 50/60Hz
Display accuracy_RTD:
•At room temperature(23ºC ± 5ºC):(PV ± 0.5% or ±1ºC, select the higher one) ± 1-digit
•Out of room temperature range:(PV± 0.5% or ±2ºC, select the higher one)± 1-digit
Display accuracy_Thermocouple:
•At room temperature(23ºC ± 5ºC):(PV ± 0.5% or ±1ºC, select the higher one) ± 1-digit
•Out of room temperature range:(PV± 0.5% or ±2ºC, select the higher one)± 1-digit
Hysteresis(adjustable sensitivity): 1 to 100℃/℉(0.1 to 50.0℃/℉) variable
Proportional band: 0.1 to 999.9℃/℉
Integral time: 0 to 9999 sec
Derivative time: 0 to 9999 sec
Control period: 0.5 to 120.0 sec
Manual reset: 0.0 to 100.0%
Environment_Ambient temperature: -10 to 50℃, storage: -20 to 60℃
Environment_Ambient humidity: 35 to 85% RH, storage: 35 to 85% RH
Insulation type: Double insulation or reinforced insulation (mark: , dielectric strength between the measuring input part and the power part: AC power 2kV, AC/DC Power 1kV)
Weight: Approx. 147g(approx. 100g)
※In case of the AC voltage model, SSR drive output method (standard ON/OFF control, cycle control, phase control) is available to select.
※Display accuracy:
At room temperature (23℃ ±5℃)
• Thermocouple R (PR), S (PR), below 200℃: (PV ±0.5% or ±3℃, select the higher one) ±1-digit
• Thermocouple R (PR), S (PR), over 200℃: (PV ±0.5% or ±2℃, select the higher one) ±1-digit
• Thermocouple L (IC), RTD Cu50Ω: (PV ±0.5% or ±2℃, select the higher one) ±1-digit
Out of room temperature range
• Thermocouple R (PR), S (PR), below 200℃: (PV ±1.0% or ±6℃, select the higher one) ±1-digit
• Thermocouple R (PR), S (PR), over 200℃: (PV ±0.5% or ±5℃, select the higher one ±1-digit
• Thermocouple L (IC), RTD Cu50Ω: (PV ±0.5% or ±3℃, select the higher one) ±1-digit
For TCN4S-□-P, add ±1℃ by accuracy standard.
※The weight includes packaging. The weight in parenthesis is for unit only.
※Environment resistance is rated at no freezing or condensation.